The perfect solution to an age old problem. The Firestem™ Fire Stop Barrier System is a mineral board, treated with an ablative coating on both sides, for fire and smoke sealing of openings in fire compartment walls and floors to give a fire resistance from 1 to 6 hours.


Coated out 200mm to provide insulation to services.

Friction fitted.

Mastic used at substrate junctions and at services penetrations.

The Firestem™ Fire Stop Barrier Systems are extremely versatile lightweight and self-supporting; no shuttering required, no mess, fast to install and highly cost effective.

Acoustic Performance

A single board system has a sound reduction index of 30dB, tested to BS5821 (1984).

A double board system has a sound reduction index of 41dB.

However, as site conditions may vary it is advisable to consult our Technical Department for specific application.

Firestem™ F60 System

The openings and cable penetrations which require to be Fire Rated to a minimum of 60 minutes are treated with a coat of Firestem™ 1W, around the opening over a width of 40mm and over the services for a length of 200mm, measured from the heart of the opening (total length of services treated with Firestem™ 1W 2 x 200 = 400mm). Any gaps between cables are filled on site with Firestem™ 2.

The opening is then sealed with sheets of mineral wool boards, 50mm thick and a density of 160 kg/m3. The mineral wool is treated on both sides with Firestem™ 1W (approximately 0.75mm thick - 1 litre/m²). Gaps between cables and the mineral wool boards are sealed with mineral wool fitted tightly around the cables. These small pieces are treated with Firestem™ 1W and glued in position.

The remaining voids between cables and cabletrays are filled with Firestem™ Mastic over a length of 100mm on both sides of the opening. After the opening is totally sealed, it is given a final coat of Firestem™ 1W.




download file now .....
get Acrobat Reader now .....



Certification

The Firestem™ Fire Stop Barrier Systems have been tested by Warrington Fire Research to BS476 part 20 and can offer the insulation and integrity criteria of this standard for up to 6 hours.



Advantages


- Gas and smoke tight

- Fire resistant and fully tested up to 6 hours (BS476 Part 20)

- Easily installed

- Low smoke emission

- Lightweight

- Simple to retrofit additional services

- Suitable for use in both plasterboard and masonry walls