The Firestem™ Fire Plug Pillow is an extremely versatile, fast method of sealing holes or openings around cable trays, or pipes in floors or walls to prevent the passage of fire between compartments. When renovations are carried out, necessitating "poke throughs" being made in walls or floors, these holes are sometimes left overnight. The Firestem™ Fire Plug Pillow is the perfect solution.


Service penetration.

Long dimensions through wall.

Joints staggered between each layer.

The pillow consists of a bag filled with an intumescent material which expands on exposure to heat sealing off the opening.

Features:

- Rated up to 4 hours fire resistance.

- Unlimited re-use if not subjected to fire.

- Ideal where cable systems are frequently re-routed.

- Dust free for use in high cleanliness environments.

Installation

In 1 hour situations, the pillows are installed with the 200mm dimension through the wall. For 1½ to 4 hour applications, the pillows are installed with the 300mm dimension through the wall. Before placing the pillows in position ensure that the filling material is evenly distributed throughout the pillow by patting the pillow flat.

Specification

Firestem™ Fire Plug Pillows come in the following sizes:-

300mm x 50mm x 35mm
300mm x 100mm x 35mm
300mm x 150mm x 35mm
300mm x 200mm x 35mm

Further sizes available on request.




download file now .....
get Acrobat Reader now .....



Certification

The
Firestem™ Fire Plug Pillow has been tested by Warrington Fire Research to BS476 part 20 and achieved in excess of 4 hours integrity and insulation.


Advantages


- Rated up to 4 hours fire resistance

- Unlimited re-use if not subjected to damage or fire

- Ideal where cable systems are frequently re-routed for temporary overnight use

- Lightweight and easy to install

- Dust free for use in high cleanliness environments




© Firestem Limited - welcome | the business | our people | useful links | contact details ::